File monitoring-plugins-ups_health.changes of Package monitoring-plugins-ups_health
-------------------------------------------------------------------
Sun Oct 05 16:20:42 UTC 2025 - Martin Hauke <mardnh@gmx.de>
- Update to version 4.3.2.3:
* improve Liebert uptime text with revision/model, make an
existing, but empty APC Powernet fall back to UPS-MIB
* fix undef messages because a "PowerNet SNMP Agent SW v2.2
compatible" is missing some OIDs.
* add active check for liebert output source instead of
condition.
* fix autoconf version.
* update liebert flexible, discover another temperature.
* fix liebert flexible temperatures, add cabinet temperature,
respect warnings/criticalx.
* fix thresholds for XUPS without internal upper/lower oids.
* fix external thresholds for Liebert Flex temperatures.
* handle external thresholds for Liebert Flex temperatures,
which have no builtn thresholds.
-------------------------------------------------------------------
Wed Sep 18 18:50:51 UTC 2024 - mardnh@gmx.de
- Update to version 4.3
* improve and fix Liebert Flexible temperatures, add humidity
- Update to version 4.2.1
* show PowerNet temperatures and humidity sensors
- Update to version 4.2
* fix apc missing battery remaining time
* fix apc missing last diagnostics time
* add EATON ATS2
* add temperatures for Liebert
- Update to version 4.1.1.1
* fix uninitialized-warnings because some liebert devices don't
return all oids
- Update to version 4.1.1
* add temperatures for Liebert (or Vertiv or irgendein
umgelabelter Schrott, ueber den schon fuenf Hersteller
gerutscht sind)
- Update to version 4.1
* reorg UPS components
- Update to version 4.0.0.1
* XUPS alarms are critical up to half a year now
- Update to version 4.0
* bugfix in XUPS-MIB alarms
* rewrite the plugin to make it epn-ready
- Update to version 3.1
* updated LIEBERT-MIBs
- Update to version 3.0.5.1
* disable lgpFlexibleBasicTable (was unused, caused timeouts)
- Add patch:
* lower-autoconf-version-requirement.patch
-------------------------------------------------------------------
Sat Jan 14 14:02:24 UTC 2023 - Martin Hauke <mardnh@gmx.de>
- Update to version 3.0.5
* support eConversion mode for PowerNet based devices (Schneider
for example).
-------------------------------------------------------------------
Tue May 3 18:54:36 UTC 2022 - Martin Hauke <mardnh@gmx.de>
- Update to version 3.0.4.1
* bugfix in liebert selftest start time (only the text output
was wrong)
* improve initial uptime-handshake
* bugfix in XPPC, get input voltage from UPS-MIB
* bugfix in UPS battery temperature
* update LIEBERT
* update GLPlugin
-------------------------------------------------------------------
Mon Dec 27 10:49:48 UTC 2021 - Martin Hauke <mardnh@gmx.de>
- Update to 3.0.3
* bugfix in XPPC, get input voltage from UPS-MIB
-------------------------------------------------------------------
Mon Dec 6 20:53:31 UTC 2021 - Martin Hauke <mardnh@gmx.de>
- Update to 3.0.2
* bugfix in UPS battery temperature
* update LIEBERT
* update GLPlugin
* add diag dump to check selftest time
* add more tracing information for Powermib, update GLPlugin
* increase the time again, 7 hours
* increase recovery time after a selftest to 6 hours (APC
Powermib)
* bugfixes in UPS and Liebert-GP (avoid undefined errors)
* fix the class inheritance, lower thresholds for powernet 4
hours after a selftest
* add EPPC-MIB
-------------------------------------------------------------------
Wed Mar 10 20:56:46 UTC 2021 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.9.2.7
* no bulk requests for Socomec Netvision, plugin may hang
-------------------------------------------------------------------
Tue Mar 9 20:38:58 UTC 2021 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.9.2.5
* updated glplugin
* fixes error for apc powernet and capacity during selftest
* more logging output for liebert
-------------------------------------------------------------------
Sun Feb 28 12:52:12 UTC 2021 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.9.2.4
* suppress battery temperature for APC Powernet if undefined
-------------------------------------------------------------------
Mon Feb 22 07:14:21 UTC 2021 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.9.2.3
* ignore very low battery temperatures for ups-mib (cs141 with
empty slot)
* lower capacity thresholds during selftest for APC Powermib
* fix Liebert detection, fix a NaN temperature value in Liebert
-------------------------------------------------------------------
Tue Oct 6 20:40:25 UTC 2020 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.9.2
* update glplugin
* fix xppc selftests without a test date (tests may not be
available at all)
-------------------------------------------------------------------
Tue Sep 8 19:25:49 UTC 2020 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.9.1
* bugfix in XUPS thresholds
-------------------------------------------------------------------
Sun May 31 17:26:24 UTC 2020 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.9
* add ATS-THREEPHASE-MIB
-------------------------------------------------------------------
Tue May 19 19:30:35 UTC 2020 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.8.3.9
* Powernet-MIB onBattery is ok when running a selftest
-------------------------------------------------------------------
Fri Apr 17 19:56:34 UTC 2020 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.8.3.8
* suppress battery temperature for UPS-MIB if an invalid number
is shown
* update GLPlugin
-------------------------------------------------------------------
Mon Nov 18 19:19:58 UTC 2019 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.8.3.6
* don't use undef XUPS thresholds
-------------------------------------------------------------------
Fri Nov 15 19:38:27 UTC 2019 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.8.3.5
* exclude unknown temp sensor for RUD101 mgmt cards
-------------------------------------------------------------------
Tue Oct 22 21:38:30 UTC 2019 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.8.3.4
* fix false positive in UPS-MIB (remainingminutes and x-thresholds)
-------------------------------------------------------------------
Mon Mar 25 22:40:54 UTC 2019 - Martin Hauke <mardnh@gmx.de>
- Update to version 2.8.3.3
* skip ampty alarms in UPS-MIB
* fix a bug in UPS-MIB for AEG Protect 1.100
* update glplugin (apc firmware bug)
* add amb/remote temp/hum to xups
* fix liebert temperature label
* xppc standby mode is ok
* update GLPlugin
- Run spec-cleaner
-------------------------------------------------------------------
Tue Jul 11 09:39:59 UTC 2017 - mardnh@gmx.de
- Update to version 2.8.1.1
* finish liebert/ups mixed emerson in dubai
* fix variable in non-standalone
* filter ups-mib alarms
* remove unnecessary alarm info
* fix xups selftest alarm
* fix cs-121 output when on battery (Thanks k0ste)
* add Emerson Liebert
* fix generex trimod without mib-2
* update GLPlugin/Extraopts
* fix UPS for Generex cs141
* update GLPlugin
* bugfix in ups-mib batterytemperature
* add glplugin submodule
* minor bugfixes
* supports dynamic mib loading
* bugfix for apc powernet. no battery status means ok
* bugfix for apc powernet. noTransfer input ok, if battery 100% full
* bugfix in Socomec Netvision detection
-------------------------------------------------------------------
Fri Sep 25 10:28:26 UTC 2015 - mardnh@gmx.de
- initial package